Design:
Housing made of Makralon for wall mountingDimensions:
185 x 120 x 90 mm (LxWxH)Connection
Plug-in screw terminalswire cross-section max. 2.5 mm
Connection for L-probe:
1 m cable with plug and couplingCable feeds:
Three PG 9 screw connectionsAuxiliary voltage:
115 or 230 Vac ± 10% / 50-60 Hz, max. 50 VAInput measuring probe:
0 … 1300 mVdc (L probe signal)Output probe:
0 … 1300 mVdc (L-probe signal, 1: 1)Option: current output galvanically isolated
0 … 20 mA or 4 … 20 mA
Output power pack:
12.00 Vdc, max. 3 A, Tol. ± 20 mV(heating voltage for L-probe)
Permissible line resistance:
Max. 1 ohmClimate:
Storage: -10 … + 70 ° COperation: 0 … + 50 ° C
5 … 95% rel. Moisture, free of condensation
OUR PRODUCT IN THE INDUSTRY
This unit is for use in the heat treatment industry, boiler industry, combustion industry, semiconductor industry, aluminium industry and control of endogas generators.