CONTROL ACCESSORY TYPE: RZ

  • Connection to Rekumat burners (RB) or Rekumat radiant tube burners (RS)
  • Screw type or mounting rail fastening
  • Overtemperature input
  • Power dosing input
  • Adjustable burner on time
  • Function display by LEDs

The Control Accessory is used in connection with a Rekumat burner (RB) or Rekumat radiant tube burner (RS) to calculate the switch on time of the built-in twoposition controller in the controlled member.

The ON time of the burner corresponds to the process conditions.

The control accessory is equippedped with a microprocessor that calculates the power requirements.

Different function versions are available.

RZ-RS (Rekumat radiant tube burner)

Construction:

Plastic housing with open terminals, alternatively with screw fastening (DIN 46121) or snap fastening
(mounting railDIN46277)

Dimensions:

150 x 70 x 112 mm (wxhxd)

Installation position:

any

Auxiliary voltage:

115 / 230 Vac ± 10 % / 50 – 60 Hz

Power consumption:

approx. 8 VA

Input:

Controllercontact(workingcontact):
The contact must be potential-free and is loaded with approx. 20 mA
Analog input: Thermoelement NiCr-Ni with automatic reference point compensation

Output:

1 radiant tube burner connection (one changeover contact each for the solenoid valves “Gas” and “Air”).
The contacts are potential-free and can be loaded withamax.1A/max.250Vacor max.0,2A/125Vac, max.2A/30Vdc according to type.

Burner ON time in all-round operation:

30 s (adjustable between 23 and 37 s in case of overtemperature monitoring)

Air rinsing time:

2 s (adjustable from 1…2 s)

Overtemperature monitoring:

Overtemperature adjustable from 1000…1200 °C, the gas valve is switched off and the air valve on after detecting overtemperature.

Power dosing:

in ranges 850…1000 °C or 950…1100 °C
power reduction from 100% to 50% (quasi-continuous)

Perm.ambienttemperature

0…50 °C

RZ-RB (Rekumat burner)

Construction:

Plastic housing with open terminals, alternatively with screw fastening (DIN 46121) or snap fastening (mounting railDIN46277)

Dimensions:

150 x 70 x 112 mm (wxhxd)

Installation position:

any

Auxiliary voltage:

115 / 230 Vac ± 10 % / 50 – 60 Hz

Power consumption:

approx. 8 VA

Input:

Controllercontact(workingcontact):
The contact must be potential-free and is loaded with approx. 20 mA
Analog input:
Thermoelement NiCr-Ni with automatic reference point compensation

Output:

1 radiant tube burner connection (one changeover contact each for the solenoid valves “Gas” and “Air”).
The contacts are potential-free and can be loaded withamax.1A/max.250Vacor max.0,2A/125Vac, max.2A/30Vdc according to type.

Burner ON time in all-round operation:

15 s (adjustable between 8 and 23 s in case of overtemperature monitoring)

Air rinsing time:

1 s (adjustable from 0.5…1 s)

Overtemperature monitoring:

Overtemperature adjustable from 1000…1200 °C, the gas valve is switched off and the air valve on after detecting overtemperature.

Perm. ambient temperature:

0…50 °C