Design:
Plastic housing for switch panel mountingDegree of Protection – front:
NEMA4 for usage in confined spaces (corresponds to the degree of protection IP66)Degree of Protection – back:
Degree of protection according to IEC standard: IP20Clamps:
Degree of protection according to IEC standard: IP20Dimensions:
96 x 96 x 115 mm (WxHxD)Front panel:
92 x 92 mm (WxH)Connection:
Screw connection. Wire cross section max. 2.5 mmAuxiliary voltage:
100 … 240 Vac, -15 + 10%, 50/60 HzPower consumption:
Approx. 16 VAClimate storage:
-10 … + 70 ° COperation:
0 … + 50 ° C, 5 … 95% rel. moisture, non- condensingDisplay:
Two 4-digit seven-segment displays for PV and SVHeights of digits:
PV = 15 mm redSV = 11mm green
Input 1:
Thermocouple types K, J, T, E, L, U, N, R, S, B, W or PLIIResistance thermometer JPt 100, PT100
Voltage input: 0 … 5 V, 1 … 5 V, 1 … 10 V, (Ri> = 1 MOhm)
Current input: 0 … 20 mA, 4 … 20 mA (Ri = 150 Ohm)
Input 2:
Decentralized set value 4…20 mA (Ri = 150 Ohm)Controller output:
(depending on integrated module)Relay output:
(potential-free contact)Voltage output:
(active, pulse, 12 Vdc or 24 Vdc [NPN] / 24 Vdc [PNP])Current output:
(continuous 4 … 20 mA or 0 … 20 mA)Alarm output:
Max. 3 alarm outputs each with 11 different alarm modes (with two-point controller)Setting:
Digital adjustment with function keysControl behavior: ON/OFF or PID-control with auto tuning
Proportional part: 0.1 … 999.9 %
FS Integral time: 0 … 3999 s
Differential: 0 … 3999 s
Other features:
Sensor calibrationAdjustable switching frequency (output cycle)
Selectable output for standard and reverse operation
Upper and lower limit for set value
Modulating controller configurable
OUR PRODUCT IN THE INDUSTRY
This unit is for use in any type of industry.