DIGITAL UNIVERSAL CONTROLER MESA

 

ADVANTAGES:

  • Self-optimizing PID-controller with the adjustable fuzzy rate
  • High accuracy (± 0.2%)
  • Exchangeable output modules
  • 3 freely definable alarm outputs
  • Ext. set value input 4 … 20 mA
  • Modular construction
  • 100 ms detection time for analog inputs

  • Decentralized set value setting
  • Serial communication via RS-232C, RS422, or RS-485 and transmission output (4…20 mA)
  • Step control
  • Heating and cooling control
  • Program regulation possible
DIGITAL UNIVERSAL REGLER MESA

TECHNICAL DATA

 

Design: Plastic housing for switch panel mounting
Degree of Protection – front: NEMA4 for usage in confined spaces (corresponds to the degree of protection IP66)
Degree of Protection – back: Degree of protection according to IEC standard: IP20
Clamps: Degree of protection according to IEC standard: IP20
Dimensions: 96 x 96 x 115 mm (WxHxD)
Front panel: 92 x 92 mm (WxH)
Connection: Screw connection. Wire cross section max. 2.5 mm
Auxiliary voltage: 100 … 240 Vac, -15 + 10%, 50/60 Hz
Power consumption: Approx. 16 VA
Climate storage: -10 … + 70 ° C
Operation: 0 … + 50 ° C, 5 … 95% rel. moisture, non- condensing
Display: Two 4-digit seven-segment displays for PV and SV
Heights of digits: PV = 15 mm red
SV = 11mm green
Input 1: Thermocouple types K, J, T, E, L, U, N, R, S, B, W or PLII
Resistance thermometer JPt 100, PT100
Voltage input: 0 … 5 V, 1 … 5 V, 1 … 10 V, (Ri> = 1 MOhm)
Current input: 0 … 20 mA, 4 … 20 mA (Ri = 150 Ohm)
Input 2: Decentralized set value 4…20 mA (Ri = 150 Ohm)
Controller output: (depending on integrated module)
Relay output: (potential-free contact)
Voltage output: (active, pulse, 12 Vdc or 24 Vdc [NPN] / 24 Vdc [PNP])
Current output: (continuous 4 … 20 mA or 0 … 20 mA)
Alarm output: Max. 3 alarm outputs each with 11 different alarm modes (with two-point controller)
Setting: Digital adjustment with function keys
Control behavior: ON/OFF or PID-control with auto tuning
Proportional part: 0.1 … 999.9 %
FS Integral time: 0 … 3999 s
Differential: 0 … 3999 s
Other features: Sensor calibration
Adjustable switching frequency (output cycle)
Selectable output for standard and reverse operation
Upper and lower limit for set value
Modulating controller configurable